Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0823-00919
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/25/2023 | Fire New Construction | REQUIRES RESUBMIT | Provide sprinkler coverage at exterior combustible concealed spaces at North and East sides of the building. Refer to acceptable omissions, NFPA 13, 2016ed. 8.15.1.2. | ||
08/21/2023 | TFD Application Completeness Check | REVIEW COMPLETED |