Permit Number: TF-FCP-0726-00491
Parcel: 13213034D

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0726-00491
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Fire New Construction - Standard REQUIRES RESUBMIT Correct coverage at full height walls in accordance with NFPA 13, 2022 ed. 9.3.14.3:
Where there is a noncombustible space above a noncombustible or limited-combustible drop ceiling that is sprinklered because it is open to an adjacent sprinklered space and where there is no possibility for storage above the drop ceiling, the sprinkler system shall be permitted to extend only as far into the space as 0.6 times the square root of the design area of the sprinkler system in the adjacent space.
Questions: patricia.shelton@tucsonaz.gov
07/29/2026 TFD Application Completeness Check Express REVIEW COMPLETED