Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0726-00489
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Fire Sprinkler (FS) Reviewer Steven Taulbee; staulbee@safebuilt.com Discipline Status:Denied Date Completed: 8/23/2026 General Comments: 1. Sprinkler Plans, FP-1. Provide Fire Sprinkler Protection in Room 97 and 98 or provide details as to how they meet the omission locations. 2022 NFPA 13, 9.1.(Resolved 08/23/26). 2. Hydraulic Calculation Summary Sheets are missing information to reflect what is on the plans for Hydraulic Information for several areas. Please provide information on Hydraulic Calculation Summary Sheets to reflect what is shown on the plans. 2022 NFPA 13, 28.4. |
||
| 08/11/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |