Permit Number: TF-FCP-0726-00489
Parcel: 115080950

Address:
1136 N STONE AV

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0726-00489
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2026 Fire New Construction - Standard REQUIRES RESUBMIT Fire Sprinkler (FS) Reviewer
Steven Taulbee; staulbee@safebuilt.com
Discipline Status:Denied
Date Completed: 8/23/2026
General Comments:
1. Sprinkler Plans, FP-1. Provide Fire Sprinkler Protection in Room 97 and 98 or provide details as to how they meet the
omission locations. 2022 NFPA 13, 9.1.(Resolved 08/23/26).
2. Hydraulic Calculation Summary Sheets are missing information to reflect what is on the plans for Hydraulic Information for
several areas. Please provide information on Hydraulic Calculation Summary Sheets to reflect what is shown on the plans.
2022 NFPA 13, 28.4.
08/11/2026 TFD Application Completeness Check Express REVIEW COMPLETED