Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0726-00488
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Battery calculation provided shows a "derating factor" of 1.20, giving a result of 6.93Ah. *Per 2022 NFPA 72 section 10.6.7.2.14, a minimum safety factor of 1.25 is to be used giving an Ah rating of over the supplied 7Ah battery. Please revise calculation and supplied battery. *Also, please denote which of the three communicator models is to be used from the provided cut sheet. Questions? Ryan P Johnson Ryan.Johnson@Tucsonaz.gov |
||