Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2026 Fire New Construction - Standard REQUIRES RESUBMIT Battery calculation provided shows a "derating factor" of 1.20, giving a result of 6.93Ah.
*Per 2022 NFPA 72 section 10.6.7.2.14, a minimum safety factor of 1.25 is to be used giving an Ah rating of over the supplied 7Ah battery. Please revise calculation and supplied battery.
*Also, please denote which of the three communicator models is to be used from the provided cut sheet.