Permit Number: TF-FCP-0726-00488
Parcel: 10925050A

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0726-00488
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2026 Fire New Construction - Standard REQUIRES RESUBMIT Cut sheet for new equipment provided.
*Since the unit specified is powered by an existing panel, a new battery calculation must be submitted proving the current existing backup battery is sufficient to run the current existing panel, existing equipment and proposed communicator.
*Please also provide a current UL Certificate of Compliance from the monitoring company.

Questions:
Ryan P Johnson
Tucson Fire Department
Fire Plans Examiner
email: Ryan.Johnson@Tucsonaz.gov
07/29/2026 TFD Application Completeness Check Express REVIEW COMPLETED