Permit Number: TF-FCP-0726-00452
Parcel: 133231340

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0726-00452
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2026 Fire New Construction - Standard REQUIRES RESUBMIT I'm looking at the battery calc's and see that the annunciator isn't there. The spec sheets submitted show the communicator as an SLE- Max2 series while the plans show the SLE-LTEV-CFB-PS communicator. I'm also seeing that the communicator is in both the FACP battery calc and the RPS 1 battery calc, but both also show it isn't using ANY power at all in either standby or alarm status. ??? I'm a little confused with all this. Feel free to reach out to me with any questions or explanations if these are in fact correct.
Ryan Johnson
ryan.johnson@tucsonaz.gov