Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TF-FCP-0726-00448
Parcel: 11011176E

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0726-00448
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please provide :
*A scalable drawing so I can verify and charge you for just the involved square footages instead of the entire 50,000sf facility, since more than the allowable 20 devices are being added.
*UL Certificate of Compliance for monitoring company to be used.
*Battery calcs and voltage drop calcs proving these new devices can be powered in addition to the existing devices using the existing battery. Note on plans says these will be provided by contractor. No permit will be issued without these added to submittal.
07/14/2026 TFD Application Completeness Check Express REVIEW COMPLETED