Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0726-00448
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Please provide : *A scalable drawing so I can verify and charge you for just the involved square footages instead of the entire 50,000sf facility, since more than the allowable 20 devices are being added. *UL Certificate of Compliance for monitoring company to be used. *Battery calcs and voltage drop calcs proving these new devices can be powered in addition to the existing devices using the existing battery. Note on plans says these will be provided by contractor. No permit will be issued without these added to submittal. |
||
| 07/14/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |