Review Details: FIRE CONSTRUCTION REVIEW REVISION v.1
Permit Number - TF-FCP-0726-00440
Review Name: FIRE CONSTRUCTION REVIEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2026 | Fire New Construction | REQUIRES RESUBMIT | *Please provide total building occupancy number to determine alarm requirements for Group E occupancy type. (2024 IFC 907.2.3 (2)) *Per 2024 IFC Section 903.4.2, Alarm, supervisory, and trouble signals shall be distinctly different and shall be automatically transmitted to an approved supervising station or, where approved by the fire code official... *Please separate the alarm, supervisory, and trouble signals on the "sequence of operation" on page FA-001 to reflect this code requirement instead of sending a single generic signal that encompasses all of these. *Please include in resubmittal a copy of the monitoring company's UL Certificate of Compliance (or similar). |
||
| 09/01/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |