Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0725-00590
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | -These appear to be two separate submittals. One submittal for sprinkler monitoring and one submittal for CO2 gas detection alarm. Please resolve with our permit tech. Should be two separate submittals. -CO2 gas detection alarm needs to be interconnected to the fire alarm control panel and needs to send a general alarm upon high activation. You CO2 sheet states only the owner will be notified. If you use a separate panel for the CO2 gas detection, it needs to be listed for commercial fire and not just a burg panel. john.vincent@tucsonaz.gov 5203495581 |
||
| 09/15/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |