Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0724-00579
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/09/2024 | Fire New Construction | REQUIRES RESUBMIT | Check spacing at North corridor on floors 2 and 3. If standpipe is supplied at the east stairwell, the two most remote connections would be located at the west stairwell. Provide Tucson Water Model. Provide air vent. Where there are uprights, please show full height walls, call out areas without protection, etc. Please call to discuss if you have any questions. Questions: patricia.shelton@tucsonaz.gov / 520.837.7082 |
||
07/23/2024 | TFD Application Completeness Check | REVIEW COMPLETED |