Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TF-FCP-0626-00406
Parcel: 12112417C

Address:
5458 E PIMA ST

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0626-00406
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please explain why existing building isn't fully protected with upright sprinklers. (28.1.3)
General note 2, states backflow is being provided, but riser detail does not match.
Provide hanger detail for new bulk main.
Provide site plan, information/dimensions shown do not match record drawings.
Questions: patricia.shelton@tucsonaz.gov
06/23/2026 TFD Application Completeness Check Express REVIEW COMPLETED