Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2026 Fire New Construction - Standard REQUIRES RESUBMIT Need to specify which dialer model will actually be installed. Also need to include battery calculations with desired backup battery to be installed for dialer.
06/11/2026 TFD Application Completeness Check Express REVIEW COMPLETED