Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0625-00497
Parcel: 10408051C

Address:
4585 N ORACLE RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0625-00497
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2025 Fire New Construction - Standard REQUIRES RESUBMIT -Correct the piping plan on sheet FS01. It appears your piping plan and nozzle information table on same sheet, do not correspond with the appropriate tanks. For example, the piping plan shows the duct and plenum nozzles on tank 1, however the table shows these nozzles on tank 2.
john.vincent@tucsonaz.gov
5203495581
07/21/2025 TFD Application Completeness Check Express REVIEW COMPLETED