Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0625-00497
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | -Correct the piping plan on sheet FS01. It appears your piping plan and nozzle information table on same sheet, do not correspond with the appropriate tanks. For example, the piping plan shows the duct and plenum nozzles on tank 1, however the table shows these nozzles on tank 2. john.vincent@tucsonaz.gov 5203495581 |
||
| 07/21/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |