Permit Number: TF-FCP-0625-00477
Parcel: 132131290

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0625-00477
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2025 Fire New Construction - Standard REQUIRES RESUBMIT Please refer to the requirements of NFPA 13, 28.1.3, for requirements for submittals. Please provide area identification, ceiling heights, location of full-height walls, etc. Provide storage criteria for ESFR sprinklers (commodity, type, etc.). Head spacing at multiple locations exceeds allowable spacing. Include area increase at applicable hydraulic calculations to meet the requirements of NFPA 13, 19.2.3.2.4.
For large drawings, a key plan or overall plan is often recommended for ease of review of spacing, calculations, etc.
Questions: patricia.shelton@tucsonaz.gov
06/23/2025 TFD Application Completeness Check Express REVIEW COMPLETED