Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0625-00465
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | Upright sprinkler spacing at box soffit, not addressed.Please include the type of structure (appears to be un-obstructed, combustible construction), meaning existing uprights (hard to determine what is an existing upright vs. existing pendent with the same symbol being used), exceed allowable spacing. Questions: patricia.shelton@tucsonaz.gov |
||
| 06/17/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |