Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0624-00469
Parcel: 11508090A

Address:
110 E HELEN ST

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0624-00469
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2024 Fire New Construction REQUIRES RESUBMIT Please revise plans and calculations for 1½" underground. The meter size will need to be increased to accommodate flow or provide an ASV for domestic water. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/tucson-water/documents/signed_meter_sizing_guidelines_march_2020.pdf
06/18/2024 TFD Application Completeness Check REVIEW COMPLETED