Permit Number: TF-FCP-0623-00802
Parcel: 132131280

Address:
3434 S KINO PW

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0623-00802
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2023 Fire New Construction REQUIRES RESUBMIT -Sheet 1/6 nozzle summary is missing plenum nozzle.
-Sheet 1/6, tank 2 missing one point (plenum nozzle). Should show 11 points for tank 2.
-Sheet 1/6 shows nozzle heights for fryers at 27"-47". Nozzle height should be 25"-35" per your detail on sheet 4/6.

john.vincent@tucsonaz.gov
5203495581
06/27/2023 TFD Application Completeness Check Express REVIEW COMPLETED