Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0623-00797
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2023 | Fire New Construction | REQUIRES RESUBMIT | -Provide documentation from captiveaire/TANK that these appliances do not need dedicated protection. Tank manual states pizza ovens, broilers, salamanders required dedicated protection. I cannot find anything in the manual specific to these small pizza conveyor ovens. Thank you, john.vincent@tucsonaz.gov 5203495581 |
||
07/19/2023 | TFD Application Completeness Check | REVIEW COMPLETED |