Permit Number: TF-FCP-0525-00417
Parcel: 10408051C

Address:
4585 N ORACLE RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0525-00417
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2025 Fire New Construction - Standard REQUIRES RESUBMIT -TFD requires the high alarm to be transmitted to a listed central station that will dispatch units on a high alarm.
-CO2 alarm shall be interconnected to the building FACP
john.vincent@tucsonaz.gov
5203495581
07/09/2025 TFD Application Completeness Check Express REVIEW COMPLETED