Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0525-00417
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | -TFD requires the high alarm to be transmitted to a listed central station that will dispatch units on a high alarm. -CO2 alarm shall be interconnected to the building FACP john.vincent@tucsonaz.gov 5203495581 |
||