Permit Review Detail
Review Status: Approved
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0525-00381
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2025 | Fire New Construction - Standard | REVIEW COMPLETED | Per section 903.4.1 and 4.3 2024 IFC: Valves controlling the water supply for automatic sprinkler systems shall be monitored by the local fire alarm. Add back flow valves to alarm and sequence of operations before inspection. Add an all weather horn strobe outside of the fire riser room per the 2024 IFC section 903.4.3 |
||
| 05/13/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |