Permit Number: TF-FCP-0525-00381
Parcel: 13815015C

Address:
6675 S 12TH AV

Review Status: Approved

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0525-00381
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2025 Fire New Construction - Standard REVIEW COMPLETED Per section 903.4.1 and 4.3 2024 IFC: Valves controlling the water supply for automatic sprinkler systems shall be monitored by the local fire alarm. Add back flow valves to alarm and sequence of operations before inspection.
Add an all weather horn strobe outside of the fire riser room per the 2024 IFC section 903.4.3
05/13/2025 TFD Application Completeness Check Express REVIEW COMPLETED