Permit Number: TF-FCP-0525-00380
Parcel: 13331159E

Review Status: Approved

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0525-00380
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2025 Fire New Construction - Standard REVIEW COMPLETED Add the following before final inspection:
1. 2018 IFC section 903.4 and 903.4.1; Monitor all valves serving the fire sprinkler back flow preventer, add them to the sequence of operations and submit AS BUILTS.
The fire Alarm Monitoring system requires a separate permit.