Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0524-00352
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/20/2024 | Fire New Construction | REQUIRES RESUBMIT | -Indicate if the building has a fire alarm that is monitored. The cover sheet with that information is blank. If no fire alarm, adjust the sequence of operations. Currently states a high alarm will be transmitted to a central station. john.vincent@tucsonaz.gov 5203495581 |
||
05/14/2024 | TFD Application Completeness Check | REVIEW COMPLETED |