Permit Number: TF-FCP-0524-00352
Parcel: 132131330

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0524-00352
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2024 Fire New Construction REQUIRES RESUBMIT -Indicate if the building has a fire alarm that is monitored. The cover sheet with that information is blank. If no fire alarm, adjust the sequence of operations. Currently states a high alarm will be transmitted to a central station.
john.vincent@tucsonaz.gov
5203495581
05/14/2024 TFD Application Completeness Check REVIEW COMPLETED