Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0425-00346
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | Provide clarification as to if a fire pump is present, if it is add it to the sequence of operations. Per 2028 IFC sections 903.4 and 903.4.2 valves related to fire sprinklers back flow preventer requires fire alarm monitoring and addition to sequence of operations. |
||
| 04/30/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |