Permit Number: TF-FCP-0425-00345
Parcel: 127090190

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0425-00345
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2025 Fire New Construction - Standard REQUIRES RESUBMIT -I do not see the correction to system 5 on sheet F2. The tanks on the same sheet, floor plan, show tanks 10, 11, 12, 14 but the pipe calcs table on sheet F2 show tanks 10, 11, 12, 13.
-Sheet F2, pipe calcs chart. The chart shows system 5, tank 10, having too many flow points. Your table shows a max flow point allowed is 10 but you're using 12. Make corrections to the table.
john.vincent@tucsonaz.gov
5203495581
07/02/2025 TFD Application Completeness Check Express REVIEW COMPLETED