Permit Number: TF-FCP-0425-00345
Parcel: 127090190

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0425-00345
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2025 Fire New Construction - Standard REQUIRES RESUBMIT -Sheet F2 (pipe calculation table). System 5, tank 10. Shows BFR 15 with only 10 flows allowed and 12 flows used. Please make corrections.
-All hoods and pull stations to be labeled.
-TFD has adopted the 2024 IFC. Correct all your code references/standards to reflect the new code adopted.
john.vincent@tucsonaz.gov
5203495581
05/19/2025 TFD Application Completeness Check Express REVIEW COMPLETED