Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0425-00345
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | -Sheet F2 (pipe calculation table). System 5, tank 10. Shows BFR 15 with only 10 flows allowed and 12 flows used. Please make corrections. -All hoods and pull stations to be labeled. -TFD has adopted the 2024 IFC. Correct all your code references/standards to reflect the new code adopted. john.vincent@tucsonaz.gov 5203495581 |
||
| 05/19/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |