Permit Number: TF-FCP-0425-00344
Parcel: 130130580

Address:
3775 E 34TH ST

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0425-00344
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2025 Fire New Construction - Standard REQUIRES RESUBMIT -Review batt calcs and add all gas detection devices.
-Correct the CO2 gas detection sequence of operations. Only the 30k needs to be a general alarm. The 5k can be local and/or supervisory.
-Correct the sequence of operations for ethanol and butane.
High alarm needs to be 25% of the LEL and report as a general alarm.
Low alarm needs to be at 10% of the LEL and be a local alarm. Can report supervisory.