Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0425-00344
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | -Review batt calcs and add all gas detection devices. -Correct the CO2 gas detection sequence of operations. Only the 30k needs to be a general alarm. The 5k can be local and/or supervisory. -Correct the sequence of operations for ethanol and butane. High alarm needs to be 25% of the LEL and report as a general alarm. Low alarm needs to be at 10% of the LEL and be a local alarm. Can report supervisory. john.vincent@tucsonaz.gov 5203495581 |
||