Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0425-00334
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2025 Fire New Construction - Standard REQUIRES RESUBMIT 1. Add fire sprinklers tamper and flow to sequence of operations, building is fully sprinklered per the provided notes.
2. If the fire alarm is monitoring signals from the local Emergency Responders Radio Coverage System (2018 chapter 5, 510.4.2.5) please add them to the Drawings.
sal.erivezjr@tucsonaz.gov