Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0425-00334
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | 1. Add fire sprinklers tamper and flow to sequence of operations, building is fully sprinklered per the provided notes. 2. If the fire alarm is monitoring signals from the local Emergency Responders Radio Coverage System (2018 chapter 5, 510.4.2.5) please add them to the Drawings. sal.erivezjr@tucsonaz.gov |
||