Permit Number: TF-FCP-0425-00312
Parcel: 141185990

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0425-00312
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2025 Fire New Construction - Standard REQUIRES RESUBMIT 1. Install an all-weather horn strobe outside fire riser locations per the 2018IFC section 903.4.2
2. Show monitoring of ERRCS signals on sequence of operations for Fire Alarm.
3. Add Annunciator panel at office area for monitoring the fire alarm-ERRCS signals.
If you have additional questions, please contact me at 520539-5370. sal.erivezjr@tucsonaz.gov
04/15/2025 TFD Application Completeness Check Express REVIEW COMPLETED