Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0425-00312
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | 1. Install an all-weather horn strobe outside fire riser locations per the 2018IFC section 903.4.2 2. Show monitoring of ERRCS signals on sequence of operations for Fire Alarm. 3. Add Annunciator panel at office area for monitoring the fire alarm-ERRCS signals. If you have additional questions, please contact me at 520539-5370. sal.erivezjr@tucsonaz.gov |
||
| 04/15/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |