Permit Number: TF-FCP-0424-00292
Parcel: 13213113C

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0424-00292
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2024 Fire New Construction REQUIRES RESUBMIT Please show full height walls (if the office area walls are not full height, please add coverage)
Add coverage at 1st floor landing of Stair 2
Provide Model Flow Data from Tucson Water.
Upright sprinkler at Elevator equipment room is not connected to branch.
Provide air vent(s)
Locate FDC on plan (Knox Caps required)
Questions: patricia.shelton@tucsonaz.gov
09/03/2024 TFD Application Completeness Check REVIEW COMPLETED