Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0424-00292
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/12/2024 | Fire New Construction | REQUIRES RESUBMIT | Please show full height walls (if the office area walls are not full height, please add coverage) Add coverage at 1st floor landing of Stair 2 Provide Model Flow Data from Tucson Water. Upright sprinkler at Elevator equipment room is not connected to branch. Provide air vent(s) Locate FDC on plan (Knox Caps required) Questions: patricia.shelton@tucsonaz.gov |
||
09/03/2024 | TFD Application Completeness Check | REVIEW COMPLETED |