Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TF-FCP-0424-00284
Parcel: 13314221A

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0424-00284
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2024 Fire New Construction REQUIRES RESUBMIT -Update sequence of operations to include CO2 alarm set points per IFC 5307.3.2
5000ppm is a supervisory with local audible and visual notification.
30000ppm is a general alarm with local/visual notification and general alarm to central station.
-Show signage on plans. Signs required at each point of use.
john.vincent@tucsonaz.gov
5203495581
04/15/2024 TFD Application Completeness Check Express REVIEW COMPLETED