Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0423-00620
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/03/2023 | Fire New Construction | REQUIRES RESUBMIT | -If this is big lots on Oracle Rd. (4525 N.) Submitted with incorrect address. Correct the address on plans. -Indicate if interior has occupant notification. If so, include with drawings and calcs. -Include occupant load of big lots. IFC 907.2.7 If 500 or more, will require occupant notification if not currently installed. john.vincent@tucsonaz.gov 5203495581 |
||
05/02/2023 | TFD Application Completeness Check | REVIEW COMPLETED |