Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0423-00580
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2023 | Fire New Construction | REQUIRES RESUBMIT | Please provide a complete set of plans for review. Only sheets FP1 & FP2 were included. Provide hydraulic calculations of standpipe in accordance with NFPA 14, 2016ed. –7.8.1.2 Provide isolation valves for standpipes in accordance with NFPA 14, 2016 – 6.3.2 |
||
| 04/11/2023 | TFD Application Completeness Check Express | REVIEW COMPLETED |