Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.4
Permit Number - TF-FCP-0326-00196
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Battery calculations added to most recent submittal. However, not all devices to be connected to new panel are represented in the new battery calculation. *Please include ALL devices to be connected to new panel in battery calc of resubmittal. It would be more helpful to me (and possibly you) to see a new fire alarm riser diagram, to make sure all devices that are supposed to be connected and included are shown. |
||
| 09/29/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |