Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0326-00196
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Please include how you are meeting the requirement of the Tucson Fire Departments modifications to the 2024 IFC. 1103.1 Required construction. Is hereby AMENDED by ADDING the following paragraph: A modification that increases the area protected by a fire protection system by fifty percent, or a fire alarm control panel replacement shall be considered a new installation, and the fire alarm system shall be brought to the current performance and installation standards in accordance with 907.5. Questions: patricia.shelton@tucsonaz.gov |
||
| 03/23/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |