Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0326-00196
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please include how you are meeting the requirement of the Tucson Fire Departments modifications to the 2024 IFC. 1103.1 Required construction. Is hereby AMENDED by ADDING the following paragraph: A modification that increases the area protected by a fire protection system by fifty percent, or a fire alarm control panel replacement shall be considered a new installation, and the fire alarm system shall be brought to the current performance and installation standards in accordance with 907.5.