Permit Number: TF-FCP-0326-00190
Parcel: 133110190

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0326-00190
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please indicate how you are meeting Tucson Fire modification to the 2024, IFC. It appears this occupancy would require occupant notification, not shown on plans.
1103.1 Required construction. Is hereby AMENDED by ADDING the following paragraph:
A modification that increases the area protected by a fire protection system by fifty percent, or a fire alarm control panel replacement shall be considered a new installation, and the fire alarm system shall be brought to the current performance and installation standards in accordance with 907.5.
Questions: patricia.shelton@tucsonaz.gov
03/23/2026 TFD Application Completeness Check Express REVIEW COMPLETED