Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0325-00238
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | Notes are conflicting regarding 13r vs 13d. Please note a 1" meter is not permitted to be used for a flow greater than 50 gpm. Please check Tucson Waters design standards. Questions: patricia.shelton@tucsonaz.gov |
||
| 03/20/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |