Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0325-00201
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | Provide fire pump details/data on plan set, see 4.2.3.2, NFPA 20, 2022ed. There is no detail showing pump discharge and the system split to risers, how is the 8" routed to building 2? It is displayed with a '90dn 0-0'. Underground piping to be installed in accordance with NFPA 24, 2022ed. Please call with any questions or clarifications. Questions: patricia.shelton@tucsonaz.gov/520.837.7082 |
||
| 04/03/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |