Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0324-00208
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/28/2024 | Fire New Construction | REQUIRES RESUBMIT | Provide air vent in accordance with NFPA 13, 2016ed 7.1.5 Provide isolation valves for standpipes in accordance with NFPA 14, 2016 – 6.3.2. Specify maximum spacing of “fast” response sprinklers clearly on plan Note which sizes/locations are steel/cpvc Please reach out if you have any questions. Patricia.shelton@tucsonaz.gov 520.837.7082 |
||
03/14/2024 | TFD Application Completeness Check | REVIEW COMPLETED |