Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0226-00097
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Please provide complete building section in accordance with NFPA 13, 2016 ed 23.1.3. Clarify pipe types, steel vs. CPVC. Provide protection at Mechanical penthouse. Since this building will be installed in phases and is expected to be approved by level during construction, phasing and temp. supply. Please note that although this building is being built to the 2018 IFC, the requirements (Knox Caps, labeling of PRV's) of Chapter 11 in the 24 IFC will be required to be met prior to final. Please reach out with any questions. Patricia.shelton@tucsonaz.gov |
||
| 02/18/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |