Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0226-00097
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Per our phone conversation. Please provide air vents (NFPA 13, 2016, 8.1.5) How are you reducing pressure at pump house riser? Please provide detail. How are you reducing pressure at basement riser? Please update detail. Please include project phasing and connections information (either as a letter or on your plan set) Please reach out with any questions. Patricia.shelton@tucsonaz.gov / 520.837.7082 * Please notify me once these updates have been incorporated, so I can complete the review. |
||
| 03/31/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |