Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0225-00158
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0225-00158
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2025 Fire New Construction - Standard REQUIRES RESUBMIT Please provide water flow model from Tucson Water. TFD is currently in the 2024 IFC, please update all code references accordingly. Label ceiling heights and full height separations in accordance with NFPA 13, 22ed., 28.1.3. Verify square footage per system is labeled on plan set, as well as this contractors start of work.
Questions: patricia.shelton@tucsonaz.gov
03/04/2025 TFD Application Completeness Check Express REVIEW COMPLETED