Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0126-00022
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | - Indicate method and type of joint restraints (4.1.3) - Note indicating fire service underground to conform to NFPA 24 - Note minimum depth of bury to be _______. (30”, more if under high-weight traffic) (4.1.3) (10.4.2.2.2) - Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours (10.4.2.2) - Note system to be flushed, and flush witnessed by TFD inspector (10.10.2.1) Verify submittal does not contain any previous approval stamps. Questions: patricia.shelton@tucsonaz.gov |
||
| 02/03/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |