Permit Number: TF-FCP-0126-00022
Parcel: 132131290

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0126-00022
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2026 Fire New Construction - Standard REQUIRES RESUBMIT - Indicate method and type of joint restraints (4.1.3)
- Note indicating fire service underground to conform to NFPA 24
- Note minimum depth of bury to be _______. (30”, more if under high-weight traffic) (4.1.3) (10.4.2.2.2)
- Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours (10.4.2.2)
- Note system to be flushed, and flush witnessed by TFD inspector (10.10.2.1)
Verify submittal does not contain any previous approval stamps.
Questions: patricia.shelton@tucsonaz.gov
02/03/2026 TFD Application Completeness Check Express REVIEW COMPLETED