Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0124-00075
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2024 | Fire New Construction | REQUIRES RESUBMIT | Residence Tucson – 6226 E. Lee St. Provide ceiling heights per NFPA 13, 2016ed. 23.1.3 Provide means for forward flow testing of the backflow following NFPA 13, 2016ed. –25.2.5.1 Provide air vent in accordance with NFPA 13, 2016ed 7.1.5 Provide coverage at closets as required by NFPA 13, 2016ed. 8.1.1(4) Reference plan set for additional information. Questions: patricia.shelton@tucsonaz.gov |
||