Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0124-00074
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/07/2024 | Fire New Construction | REQUIRES RESUBMIT | Residence Tucson – 6226 E. Lee St. Provide ceiling heights per NFPA 13, 2016ed. 23.1.3 Provide means for forward flow testing of the backflow following NFPA 13, 2016ed. –25.2.5.1 Provide air vent in accordance with NFPA 13, 2016ed 7.1.5 Provide coverage at Corridor 201 (see plan set) This probably could have been addressed as an as-built but I will be requesting resubmittal on the other buildings for unrelated code issues. Questions: patricia.shelton@tucsonaz.gov |
||