Permit Number: TF-FCP-0123-00290
Parcel: 12317201C

Address:
1449 N CHERRY AV

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0123-00290
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2023 Fire New Construction REQUIRES RESUBMIT T19FC01074 - Cintas permit for monitoring is expired. Shows Starlink was installed. If Stralink is panel powered technology, it shall be in the battery calculations.
All zones show that they are being used, however, you do not show a zone for the kitchen fire suppression system?
Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/12/2023 TFD Application Completeness Check Express REVIEW COMPLETED