Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0123-00249
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2023 | Fire New Construction | PENDING ASSIGNMENT | |||
| 04/05/2023 | TFD Application Completeness Check Express | REQUIRES RESUBMIT | Plans show that you are using a 12v7ah battery but the calculations show you need a 12v 12ah battery. Plans shall show the building type and square footage. Plans shall show the location of the cellular dialer. Plans shall have a symbol/description list and attach to this permit. |