Permit Number: TF-FCP-0123-00249
Parcel: 108254820

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0123-00249
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2023 Fire New Construction REQUIRES RESUBMIT Plans show that you are using a 12v7ah battery but the calculations show you need a 12v 12ah battery. Plans shall show the building type and square footage. Plans shall show the location of the cellular dialer. Plans shall have a symbol/description list