Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0123-00249
Parcel: 108254820

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0123-00249
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2023 Fire New Construction REQUIRES RESUBMIT Plans show that you are using a 12v7ah battery but the calculations show you need a 12v 12ah battery. Plans shall show the building type and square footage. Plans shall show the location of the cellular dialer. Plans shall have a symbol/description list

Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
02/01/2023 TFD Application Completeness Check Express REVIEW COMPLETED