Permit Number: TE-FPU-1125-00409
Parcel: 138081290

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TE-FPU-1125-00409
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2026 Site Engineering Express REQUIRES RESUBMIT Permit Activity Number: TE-FPU-1125-00409 (1st Review)
Project: New Sleeping Quarters
Location: 649 W SANTA ROSA ST
Review Date: 10/19/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. Final Elevation Certificate submittal denied – The submitted elevation certificate shows that the determined base flood elevation (BFE) as 2490.62’. The sleeping quarters FFE of 2491.66’ is considered compliant per Floodplain regulations, but the elevation certificate also shows machinery and equipment (M&E) at 2490.1’ as shown on C2.e and through the photos provided. A revision will be required so that the mini-split AC units are built 1-ft above the established BFE as required for both the dwelling and all M&E for the proposed development. Ensure that resubmission accurately shows that all equipment is elevated at least 1-ft above the BFE.
2. It appears there was an error in the creation of the original form, a NEW Elevation Certificate form has been created and provided within the attachment of this FPU permit, please ensure that for resubmission the new cert form is used.